Leave Your Message

China Factory Suppliers of SCB10 10kV Class Epoxy Resin Dry-Type Transformer - Low Noise, Energy Efficient Solution

Discover the SC(B)10 epoxy resin cast dry-type transformer, a leading product manufactured in accordance with the Dry-type Power Transformers standard. This transformer showcases low performance loss and exceptional energy-saving capabilities, ensuring economical operation and maintenance-free service. Crafted in China by top suppliers, this transformer features an advanced structural design, high short-circuit resistance, and impressive lightning impulse withstand levels. With its flame-retardant, moisture-resistant, dustproof, and low-noise attributes, the SC(B)10 is ideal for integration into load centers. It's versatile and widely used in various applications, including high-rise buildings, airports, stations, docks, power plants, and substations. Particularly suitable for installation in areas with stringent fire protection requirements, such as flammable and explosive environments, this product stands out in the market. Trust in our factory to deliver quality and reliability for your electrical solutions.

    Product Features

    This epoxy resin cast dry-type transformer integrates advanced technology and high-quality materials, delivering excellent electrical performance, mechanical stability, and environmental adaptability. It is widely suitable for industrial parks, commercial complexes, municipal infrastructure, high-rise buildings, and similar applications, particularly for installation in load centers with strict requirements for safety, environmental protection, and space utilization.

    The product features a differentiated conductor design. The high-voltage winding uses high-conductivity enameled copper wire with a high-temperature-cured insulation layer, offering high dielectric strength and stability. The low-voltage winding is wound with high-purity copper foil, providing ample cross-section, enhanced current capacity, and optimized heat dissipation. The windings are vacuum-impregnated with imported unfilled epoxy resin, forming a solid, bubble-free structure after curing. This ensures high mechanical strength, resistance to short-circuit forces, and extremely low partial discharge (≤5 pC).

    The epoxy resin meets the flame-retardant requirements of GB/T 10217-2018. It is non-flammable, emits no toxic gases, and contains no volatile pollutants, allowing for safe indoor installation without a separate transformer room. The moisture-resistant insulation and specially treated core and clamps enable reliable operation in harsh conditions (e.g., 100% humidity, high temperatures, dusty environments), even after intermittent use without drying.

    The transformer exhibits strong short-circuit and lightning impulse withstand capability, along with a 120% short-term overload capacity. Its thin insulation layers and conductive materials promote efficient cooling via natural air (AN); an optional forced air (AF) system can increase cooling efficiency by over 30%. The core is made of low-loss silicon steel, reducing no-load and load losses significantly below national standards for enhanced energy savings.

    Fully sealed and maintenance-free, it eliminates oil leakage risks. Compared to traditional oil-immersed transformers, its volume and weight are reduced by over 40% and 30%, respectively, allowing flexible installation in compact spaces with minimal foundation work.

    Product Specifications

    Rated Capacity
    (KVA)
    No-load Loss
    (W)
    Load Loss
    (120℃)(W)
    Short-circuit
    Impedance(%)
    No-load Current
    (%)
    Sound Level
    (LPA)(dB)
    Weight
    (kg)
    30 360 1050 6.5 3.0 52 680
    50 440 1300 2.5 53 720
    80 510 1740 2.0 55 810
    100 650 1990 1.8 56 890
    125 750 2430 1.8 58 950
    160 850 2785 1.8 58 1000
    200 950 3040 1.8 59 1260
    250 1070 3485 1.8 59 1420
    315 1290 3840 1.6 61 1730
    400 1520 4960 1.6 62 1840
    500 1750 6080 1.4 63 2200
    630 2050 7080 1.4 63 2630
    800 2400 8400 1.2 66 3260
    1000 2690 9660 1.0 66 3990
    1250 3140 11695 0.8 67 4470
    1600 3590 14210 0.8 68 5570
    2000 4220 16730 0.7 69 6410
    2500 4940 20035 0.7 73 6930

    Detail Pictures

    Frequently Asked Questions

    What makes epoxy resin cast dry-type transformers safer for indoor installation?
    They utilize flame-retardant epoxy resin that is non-flammable, emits no toxic gases, and poses zero risk of oil leakage, making them completely safe for commercial buildings and compact spaces without requiring dedicated fireproof rooms.
    Can this transformer operate in high-humidity or harsh environments?
    Yes. The core and clamps feature specialized surface treatments, and the moisture-resistant vacuum cast winding allows the transformer to operate reliably even under 100% relative humidity, high dust levels, and extreme temperature variations without pre-drying.
    How does the cooling system work, and can capacity be increased?
    The unit comes standard with Natural Air (AN) cooling. For increased operational demand, an optional Forced Air (AF) cooling system can be installed, boosting heat dissipation efficiency by more than 30% and supporting higher short-term loads.
    How does the size and weight compare to conventional oil-immersed transformers?
    Compared to traditional oil-filled units, this dry-type design reduces overall footprint volume by more than 40% and total weight by over 30%, which significantly simplifies site civil foundation work and cuts transport costs.
    What is the partial discharge level of this transformer?
    Thanks to the vacuum resin impregnation process that eliminates air bubbles, the partial discharge level is exceptionally low, strictly controlled at or below 5 pC, ensuring a long operational lifespan and insulation stability.