Dry Type Transformer Cooling Methods: AN vs AF Explained
A dry transformer running hot does not automatically mean that its kVA rating is too small.
During commissioning, the cause can be much simpler: blocked winding air channels, insufficient transformer-room exhaust, a higher enclosure protection level, high ambient temperature, incorrect fan direction, or poorly configured temperature-control settings.
All of these conditions eventually affect winding temperature.
For this reason, understanding dry type transformer cooling methods requires more than knowing that AN means natural air and AF means forced air.
An EPC engineer should answer four questions first:
What is the real ambient temperature?
What load will the transformer carry continuously?
How long will peak loads last?
Can the installation remove the heat generated by transformer losses?
Those questions define the real dry type transformer cooling system.
Transformer kVA and thermal capability are not the same question
Core losses and winding losses eventually become heat.
For a dry transformer, that heat has to travel through several stages:
winding → winding surface → surrounding air → enclosure → transformer room → building ventilation system.
If hot air becomes trapped at any stage, transformer temperature increases.
This means a 1600 kVA nameplate does not guarantee identical thermal performance in every installation.
A transformer operating in a 28°C electrical room is not under the same thermal condition as the same unit installed in a 46°C industrial building.
A unit at 500 m altitude is not operating under the same air density as one at 2,500 m.
An IP23 ventilated enclosure does not behave thermally like a much more restricted enclosure.
This is why dry transformer temperature rise must be reviewed together with the installation environment.
IEC 60076-11:2018 remains the key IEC document for dry-type transformers within its stated scope, and the current edition specifically addresses enclosure management, altitude and thermal characteristics.
How AN natural-air cooling works
AN means:Air Natural
With natural air cooling dry type transformer designs, no main cooling fan is required to move air through the winding.
Heat raises the temperature of the air surrounding the windings. The warmer air rises naturally while cooler air enters from below.
A well-designed winding therefore contains intentional cooling ducts and clear airflow paths.
AN performance depends heavily on installation geometry.
Typical site problems include:
transformers installed too close to a wall;
bottom air inlets blocked by cables;
insufficient clearance above the transformer;
hot exhaust air returning directly to the transformer inlet;
two transformers heating each other;
poorly designed enclosure louvers;
building ventilation that cannot remove transformer losses.
AN is mechanically simple, but it requires an effective natural airflow path.
What AF forced-air cooling actually changes
AF means:Air Forced
A dry type transformer forced air cooling system uses fans to increase airflow across and through the transformer windings.
A typical AF package may include:
transformer cooling fans, PT100 temperature sensors, a temperature controller, fan relays, high-temperature alarm contacts and trip contacts.
The operating logic normally follows several temperature thresholds.
At one temperature, the fans start.
When winding temperature falls sufficiently, the fans stop.
A higher temperature produces an alarm.
A further threshold can provide a transformer trip signal.
The exact values should come from the transformer thermal design rather than being copied from another project.
Some transformer designs provide a higher permissible output with AF. For example, Eaton states that forced-air output on certain dry-transformer designs can reach up to 140% of the self-cooled rating, while also stating that this loading should not be treated as continuous normal operation.
That distinction matters.
A purchaser should not write:“1600 kVA transformer, fan overload 40%”
without confirming the manufacturer's thermal rating.
A better specification defines:
AN rating;
AF rating;
permissible operating duration;
reference ambient temperature;
fan quantity;
fan redundancy;
control and alarm logic.
AN vs AF should be decided from the load profile
The useful question behind AN vs AF cooling for dry type transformer is not simply which method provides more cooling.
It is whether the transformer experiences stable or variable loading.
Consider a 1600 kVA industrial transformer that normally carries 900–1200 kVA and occasionally reaches 1400 kVA.
AN may already provide sufficient capacity.
Now consider a commercial building or data-center transformer with predictable high-load periods every day.
AF can provide useful thermal flexibility.
A different situation occurs when a 1600 kVA transformer must rely on its fans every day to support approximately 1900–2100 kVA.
In that case, the base transformer rating itself should be reviewed.
Continuous dependence on fan-assisted uprating introduces more failure points:
fan motors;
bearings;
dust accumulation;
control relays;
temperature controllers;
auxiliary-power failure;
maintenance requirements.
For many projects, the better engineering strategy is to size the AN rating for normal continuous load and use AF for controlled peak periods or thermal reserve.
Ambient temperature can matter more than the fan configuration
When evaluating dry type transformer cooling for high ambient temperature, the project environment must be defined before production.
Normal IEC service conditions commonly use a maximum ambient-air temperature of 40°C and an altitude not exceeding 1,000 m as reference conditions, with special conditions requiring design consideration.
Suppose two 1000 kVA transformers have identical electrical ratings.
Transformer A operates in a ventilated electrical room at approximately 22–30°C.
Transformer B operates in a production building where summer temperature reaches 45–48°C.
Their thermal margins are not equivalent.
A professional RFQ should therefore specify:
Maximum ambient temperature;
average ambient temperature;
installation altitude;
indoor or outdoor location;
ventilation conditions;
required enclosure IP rating.
Without these values, the manufacturer may have to design around standard service conditions rather than the actual site.
Higher IP protection can reduce cooling performance
Purchasers sometimes request an enclosure change from IP23 to IP44 late in the project.
That appears to be a mechanical modification.
Thermally, it may be much more significant.
A higher enclosure protection level can restrict airflow.
For cast resin transformer cooling, the enclosure therefore has to be treated as part of the thermal system.
Air-inlet area, outlet area, louver geometry, internal clearance and airflow direction can all influence temperature rise.
When the enclosure configuration changes, the supplier should reconfirm:
continuous rating;
enclosure dimensions;
ventilation openings;
need for forced ventilation;
expected temperature-rise performance.
A higher IP number alone does not indicate a better transformer design.
Engineering Scenario 1: 2500 kVA transformer in a data center
Consider a typical indoor:
10 kV / 0.4 kV
2500 kVA
cast-resin dry-type transformer.
The project may select a dry transformer because of indoor installation, fire considerations and maintenance requirements.
The major cooling issue can still be outside the transformer.
If the electrical room cannot discharge transformer losses, room temperature gradually rises.
When AF fans start, they then move already-heated room air through the transformer.
AF does not replace the building ventilation system.
For this type of project, the engineer should review:
transformer losses;
room volume;
air-inlet area;
exhaust-air capacity;
mechanical ventilation or HVAC;
transformer clearances;
fan-control logic.
These factors form the practical ventilation requirements for dry type transformer room installations.
Engineering Scenario 2: 1600 kVA transformer in a hot industrial plant
Consider another common project:
11 kV / 0.415 kV
1600 kVA
Dyn11
50 Hz
indoor installation.
The transformer supplies a cement plant, steel facility, processing plant or heavy manufacturing line.
Ambient temperature may remain above 40°C for significant periods, while airborne dust is also present.
Installing stronger fans alone can create another problem.
Higher airflow may carry more dust through the transformer cooling passages.
The project therefore has to balance:temperature rise;dust protection;filtration;maintenance intervals;enclosure design;room ventilation.
In severe environments, preserving more thermal margin in the transformer rating can be safer than depending on continuous AF-assisted overload.
Dry-type vs oil-immersed transformer cooling
A useful product comparison is the difference between dry type transformer cooling and oil-immersed transformer cooling.
A dry-type transformer transfers much of its heat directly into surrounding air.
Its performance is therefore highly dependent on airflow and room conditions.
An oil-immersed transformer first transfers internal heat through insulating liquid to the tank and radiators, after which the heat is transferred to ambient air.
For projects with high ambient temperatures, outdoor installation, continuous heavy load and adequate installation space, an oil-immersed design can offer practical thermal advantages.
For indoor buildings, hospitals, airports, commercial facilities, underground installations and data centers, dry-type transformers are often selected because of their installation and fire-performance requirements.
Cooling performance should therefore be compared in the context of the project, not as an isolated product feature.
Procurement risks hidden behind the words “AN/AF”
One of the most common specification problems is a transformer datasheet that states only:
Cooling: AN/AF.
That leaves several commercial and technical risks unresolved.
First, is the AF rating an official manufacturer rating?
Do not assume every dry transformer gains 40% capacity when fans are installed.
Second, what is the maximum site ambient temperature?
A 45°C site should not be evaluated using the same thermal assumptions as a 40°C site.
Third, what is the altitude?
Lower air density at higher altitude affects cooling performance and can influence insulation design.
Fourth, has the enclosure protection level changed?
A late change in IP requirement may require a thermal review.
Fifth, what supplies the AF fans?
This last point is frequently overlooked during international procurement.
Voltage matching includes the cooling accessories
Export enquiries commonly specify transformer voltages such as:
10 kV / 0.4 kV;
11 kV / 0.415 kV;
13.8 kV / 0.48 kV;
33 kV / 0.415 kV.
An AF transformer introduces another voltage requirement:
fan and control auxiliary power.
Fans may be designed for 220 VAC, 230 VAC, 380 VAC or another specified supply.
The temperature controller also requires a compatible power source.
A complete RFQ should therefore specify:
primary voltage;
secondary voltage;
50 Hz or 60 Hz;
vector group;
tap range;
cooling method;
fan auxiliary voltage;
control voltage.
Without this check, the main transformer can arrive with the correct primary and secondary voltages while the cooling accessories remain incompatible with the site's auxiliary-power system.
What should be checked during FAT?
For dry type transformer FAT, the purchaser should inspect more than the cooling fans.
The agreed FAT programme should cover applicable IEC routine tests and project-specific functional checks.
Depending on the applicable specification, routine electrical verification can include:
winding resistance;
voltage ratio;
phase relationship/vector group;
no-load loss and current;
load loss;
short-circuit impedance;
applicable dielectric tests.
Published dry-transformer factory-test practices from major manufacturers similarly include ratio, phase relation, no-load loss, excitation current and dielectric tests before shipment.
For an AF-equipped transformer, the FAT witness should also verify:
PT100 signals;
three-phase winding-temperature indication;
operation of each fan group;
correct airflow direction;
fan start threshold;
fan stop hysteresis;
high-temperature alarm;
trip contacts;
controller fault signals.
A temperature rise test should be identified in the purchase specification when required rather than requested only after production has been completed.
Export packing requires special attention to the cooling system
Dry transformers exported from China may pass through truck transportation, factory lifting, port handling, sea freight, destination-port unloading and inland delivery before reaching the final substation.
The transformer core-and-coil assembly is relatively robust.
Cooling accessories are often more vulnerable.
Fans, mounting brackets, temperature-control boxes and exposed wiring can be damaged by impact or vibration.
Before export shipment, the packing plan should therefore address:
fan fixation;
removal or protection of exposed components where necessary;
moisture protection for the controller;
separate packing for accessories;
identification of spare fans;
protection of sensor wiring;
desiccant or moisture-control measures;
lifting and center-of-gravity markings.
Long sea transport also requires attention to humidity and container condensation.
After arrival, the commissioning team should inspect fan rotation, wiring, temperature sensors and controller settings before energization.
How to specify the cooling method for procurement
A simple AN system is often preferable when continuous loading is stable and the installation has good ventilation.
AF provides useful operating flexibility where short-duration peak loads occur.
High ambient temperature, high altitude, restricted enclosures or poor room ventilation require a broader thermal review.
In those cases, adding fans should not be treated as the universal solution.
The engineer should reassess:
base kVA;
load profile;
temperature rise;
room heat rejection;
enclosure airflow;
site ambient temperature;
altitude;
required thermal margin.
That is the practical meaning of transformer thermal management.
FAQ
1. Does every dry-type transformer require cooling fans?
No.
Many transformers can operate continuously at their AN nameplate rating without fans. AF is normally applied when additional thermal flexibility, peak-load capability or active temperature control is required.
2. Does forced-air cooling always increase transformer capacity by 40%?
No.
The permitted increase depends on the manufacturer's thermal design. The AN and AF ratings should be confirmed from the approved technical data or nameplate.
3. Can a transformer continue operating after a cooling fan fails?
If the transformer has a defined AN rating, operation may be possible within that AN loading and temperature limit. The manufacturer's operating instructions should govern the final decision.
4. Will installing more fans solve a hot transformer room?
Not necessarily.
If hot air cannot leave the room, stronger transformer fans simply circulate hot air. Building ventilation must remove the transformer losses.
5. Why does altitude affect dry-transformer cooling?
Higher altitude means lower air density, which changes convective cooling performance. Projects above the standard reference altitude should be identified during quotation.
6. Is IP44 always better than IP23 for a dry transformer?
No.
IP44 provides greater environmental protection, but the more restricted airflow may affect thermal performance. Enclosure and transformer thermal design should be evaluated together.
7. What cooling information should I send with an RFQ?
For an accurate dry type transformer cooling system proposal, provide:
transformer kVA;
primary voltage;
secondary voltage;
frequency;
maximum ambient temperature;
altitude;
indoor or outdoor installation;
IP requirement;
continuous load;
peak load;
required AN or AN/AF operation;
fan auxiliary voltage.
Call To Action
If your project requires a dry type distribution transformer, do not send only the kVA and voltage ratio.
Provide the site ambient temperature, altitude, enclosure requirement, continuous load and peak-load profile as well.
Huamei Electric can review the electrical parameters and installation conditions before quotation and recommend the appropriate dry type transformer cooling method, AN/AF configuration, temperature-monitoring system and FAT scope for your project.
For EPC and procurement enquiries, send:
kVA
Primary / Secondary Voltage
50 / 60 Hz
Installation Country
Maximum Ambient Temperature
Altitude
Indoor / Outdoor
IP Rating
Continuous Load
Peak Load
AN or AN/AF Requirement
This allows the transformer thermal design to be confirmed before production rather than corrected during site commissioning.