Dry Type Transformer Hot Spot Temperature: Engineering Guide
Dry-Type Transformer Hot-Spot Temperature: Why Local Overheating Matters More Than Average Temperature Rise
A transformer can show an acceptable average winding temperature and still contain a much hotter local region inside the winding.
That distinction is the reason dry type transformer hot spot temperature deserves separate engineering attention from average temperature rise.
Average temperature tells an engineer how the winding behaves as a thermal system. Hot-spot temperature indicates where the insulation is experiencing its highest local thermal stress.
For EPC projects, industrial facilities and critical distribution systems, this difference affects transformer thermal design, loading decisions, ventilation, temperature monitoring and test specifications.
IEC 60076-11:2018 is the principal IEC standard specifically covering dry-type power transformers within its defined scope, including transformers with highest voltage for equipment up to 72.5 kV. Thermal requirements must still be interpreted together with the applicable transformer design, insulation system and approved project specification.

Average Winding Temperature and Hot-Spot Temperature Answer Different Questions
The temperature of a transformer winding is not uniform.
Current flowing through the conductors produces losses. At the same time, airflow, conductor geometry, resin thickness, cooling ducts and surrounding structures affect how efficiently heat can leave different parts of the winding.
An average winding temperature therefore represents the thermal condition of the winding as a whole.
A hot spot represents the locally hottest region.
The distinction can be illustrated conceptually as:
Hot-spot temperature ≈ ambient temperature + average winding temperature rise + local hot-spot differential
This is an engineering representation, not a universal IEC calculation formula. The actual relationship depends on transformer construction, loss distribution, cooling and operating conditions.
IEEE guidance for dry-type transformers specifically recognizes that assumptions relating hottest-spot temperature to average winding temperature rise are not representative of every dry-type transformer construction or winding size.
This means that an acceptable average value does not automatically prove that every section of the winding is operating at an equally safe temperature.
Why Local Temperature Can Be Higher Than the Average
A dry-type transformer does not generate or dissipate heat uniformly.
Several mechanisms can create a local thermal maximum.
Uneven winding losses
Conductor losses are influenced by current, conductor cross-section, winding geometry and AC effects.
Regions with higher local loss density can generate more heat than surrounding sections.
Stray and eddy-current effects may also create non-uniform loss distribution depending on the winding design.
Uneven cooling airflow
AN-cooled dry-type transformers depend heavily on natural air circulation.
Air entering from the lower section is heated as it moves upward. Cooling conditions therefore change throughout the winding height.
The geometry of cooling ducts and the clearance around the transformer influence this airflow.
Experimental and numerical research on dry-type transformers has shown that temperature distribution can be significantly non-uniform and that winding hot spots respond strongly to load rate.
Enclosures
An enclosure changes the thermal environment around the transformer.
The same active part installed without an enclosure and inside a restrictive enclosure should not automatically be assumed to have identical cooling performance.
Ventilation opening area, airflow path, enclosure size, IP requirement and fan arrangement all affect thermal performance.
IEC 60076-11:2018 specifically includes enclosure management among the areas addressed by the current edition.
Ambient temperature
Hot-spot temperature is an absolute temperature.
If the transformer operates with the same internal temperature rise but ambient temperature increases, the actual winding temperature also increases.
This is why RFQs should not specify only kVA and voltage.
Maximum design ambient conditions matter.
Harmonic current
Non-linear loads can increase transformer losses beyond what would be expected from fundamental-frequency RMS loading alone.
Data centers, UPS systems, variable-frequency drives, rectifiers and other power-electronic loads should therefore be evaluated using their actual harmonic characteristics.
A transformer operating below its nameplate kVA is not automatically thermally lightly loaded if its current waveform creates significant additional losses.
Blocked cooling paths or fan problems
Dust accumulation, restricted ventilation, improperly positioned panels, fan failure or incorrect fan control can increase local temperature without immediately producing an obvious electrical fault.
The effect can be especially significant where cooling margin is already limited.

Why the Hot Spot Matters to the Insulation System
Transformer insulation is exposed to electrical, mechanical, environmental and thermal stress.
Among these, local thermal stress deserves special attention because insulation aging is temperature dependent.
The temperature that matters most to the most severely stressed part of the insulation system is not necessarily the winding average.
A local region that repeatedly runs hotter than the rest of the winding may experience greater thermal aging even while average temperature readings remain acceptable.
The exact aging relationship cannot be reduced to one universal “every X°C halves life” rule for all dry-type transformers.
Cast-resin systems, VPI designs and different insulation materials may use different thermal classes and material systems.
For that reason, project engineers should distinguish between:
- insulation system temperature class;
- permitted winding temperature rise;
- maximum operating ambient;
- measured winding temperature;
- calculated or measured hot-spot temperature;
- alarm and trip settings.
These are related parameters, but they are not interchangeable.
Any allowable limit should be confirmed against the applicable standard, qualified design and approved manufacturer documentation rather than copied from another transformer project.
Average Temperature Rise Test Does Not Automatically Reveal Every Local Hot Spot
One of the most important procurement distinctions is between average winding temperature rise and direct local temperature measurement.
Winding resistance can be used to determine an average winding temperature.
This is extremely useful for transformer temperature-rise evaluation, but a resistance-derived average cannot by itself identify the exact temperature of every turn or local winding section.
This limitation has been recognized in dry-type transformer thermal research for decades. Published work specifically notes that the difference between average temperature rise by resistance and the hottest-spot temperature can be significant in dry-type windings.
For a standard distribution project, average winding temperature-rise verification may be sufficient when supported by a qualified transformer design.
For a highly loaded or thermally critical project, the purchaser may require more detailed hot-spot evaluation.
How Dry-Type Transformer Hot Spots Can Be Determined
No single measurement method solves every application.
Winding resistance method
This method is suited to determining average winding temperature.
Its main advantage is that it evaluates the winding electrically rather than relying only on one external sensor.
Its limitation is equally important: it does not provide a spatial map of local winding temperature.
Embedded RTD or Pt100 sensors
Pt100 sensors are widely used for dry-type transformer operating temperature supervision.
They can provide continuous readings for alarm, fan control and trip functions.
Their accuracy as a hot-spot indicator, however, depends heavily on sensor location.
A Pt100 measures the temperature at its installed position. It does not prove that another internal point is not hotter.
This is why sensor position should be treated as a design parameter rather than simply specifying “PT100 required.”
Infrared thermography
Infrared cameras are useful for detecting abnormal surface temperature patterns, ventilation problems, connection heating and phase-to-phase thermal differences.
Their limitation is physical access.
A thermal camera sees accessible surfaces, not every internal conductor inside a cast winding.
Research combining infrared monitoring with fixed sensors has therefore used the data as part of a broader hot-spot prediction approach rather than treating surface temperature as a perfect internal measurement.
Fiber-optic temperature measurement
Fiber-optic sensors can be embedded at selected winding locations and used for direct temperature measurement under high electromagnetic fields.
Commercial transformer monitoring systems are available specifically for real-time hot-spot measurement in dry-type and liquid-filled transformers.
Fiber-optic measurement is particularly relevant when direct internal temperature data are required during prototype validation, thermal research or critical service.
It should not be assumed necessary for every conventional distribution transformer.
Thermal network and CFD analysis
Thermal simulation is useful during transformer design because it can estimate temperature distribution before manufacturing.
Electromagnetic loss calculation can be coupled with heat transfer and airflow analysis to identify probable high-temperature regions.
For important designs, simulation should ideally be supported by physical test correlation rather than being treated as independent proof of performance.

Measurement Method Comparison
| Method | Main Output | Strength | Main Limitation |
|---|---|---|---|
| Winding resistance | Average winding temperature | Established thermal test method | Does not directly locate hot spot |
| Pt100 / RTD | Temperature at sensor location | Practical continuous monitoring | May not be located at actual hottest point |
| Infrared thermography | Surface temperature distribution | Good diagnostic tool | Cannot directly see inaccessible internal winding points |
| Fiber-optic sensor | Direct temperature at embedded location | Internal real-time measurement | Requires design integration and added cost |
| CFD / thermal model | Predicted temperature field | Useful during design | Accuracy depends on model assumptions and validation |
The appropriate method therefore depends on what the project is trying to prove.
A purchaser asking only for “temperature monitoring” has not yet defined a complete thermal monitoring requirement.
Two Engineering Situations Where Average Temperature Can Be Misleading
Scenario 1: Transformer inside a high-IP enclosure
Consider a dry-type transformer operating close to its rated load.
The transformer design itself may have acceptable thermal performance, but the project requires an enclosure with restricted openings.
If the enclosure ventilation design is inadequate, warm air can recirculate around the winding.
The average thermal condition may increase, but the more serious problem can be a specific winding region receiving substantially poorer airflow than expected.
For this application, procurement should confirm:
- transformer rating inside the specified enclosure;
- cooling method;
- ventilation arrangement;
- ambient temperature;
- required IP rating;
- fan requirements if applicable;
- temperature sensor arrangement.
A transformer rating stated for an unenclosed AN unit should not be assumed to remain unchanged after installation conditions are altered.
Scenario 2: Industrial load with significant harmonics
A transformer feeding motors through VFDs, rectifiers, UPS equipment or other non-linear loads may experience a loss distribution different from a predominantly sinusoidal-load application.
Simply checking kVA may therefore miss part of the thermal picture.
The design review should include load profile and harmonic information where relevant.
The engineering question becomes:
At the specified current waveform and duty cycle, where is the highest thermal stress expected to occur?
That is more useful than asking only whether the average load is below 100%.

AN and AF Cooling Should Be Evaluated Against Hot-Spot Conditions
Forced-air cooling can increase the available transformer loading capability when the transformer is designed and rated for that mode.
But AF cooling should not be viewed simply as “adding fans.”
Engineers should confirm:
- airflow direction;
- fan quantity and redundancy;
- fan start temperature;
- fan stop temperature;
- sensor used for fan control;
- transformer rating in AN mode;
- transformer rating in AF mode;
- allowable operating duty;
- behavior after fan failure.
A transformer required to carry the full critical load only while fans are operating creates a different system risk from a transformer capable of carrying the critical load under natural cooling.
The hot-spot condition during loss of forced ventilation should therefore be considered during project design.

What Should Be Written into the RFQ?
For projects where thermal performance matters, the RFQ should provide enough information for the manufacturer to evaluate actual hot-spot risk.
A useful thermal specification includes:
Electrical data
Rated capacity, primary voltage, secondary voltage, frequency, impedance and vector group.
Loading information
Expected continuous load, peak load, overload duration and load profile.
Load characteristics
Relevant harmonic information for major non-linear loads.
Site conditions
Maximum ambient temperature, minimum ambient temperature if relevant, altitude and installation location.
Cooling
AN, AF or other project-defined cooling requirements.
Enclosure
Required IP degree and whether the rating must be guaranteed with the transformer installed inside the specified enclosure.
Insulation system
Required thermal class and project-specific temperature-rise requirements.
Monitoring
Pt100/RTD requirements, number of channels, sensor positions, temperature controller, alarm, trip and fan-control functions.
Thermal verification
Required temperature-rise test documentation, type-test evidence or project-specific hot-spot evaluation.
For unusual loading or critical infrastructure, the RFQ may also request the manufacturer's proposed method for determining the winding hot spot.
Temperature-Rise Testing and FAT: Do Not Treat Them as the Same Thing
A common procurement mistake is to write:
“Full FAT including temperature-rise test required.”
without defining what “full FAT” means.
Routine tests, type tests and special tests should be separated in the specification.
Historical IEC 60076-11 documentation classifies the temperature-rise test as a type test rather than an automatic routine test on every transformer. The purchaser should verify requirements against the current applicable IEC edition and agreed project specification.
For a conventional order, the purchaser may accept valid type-test evidence for a qualified design.
For a critical project, the specification may require a witnessed temperature-rise test or additional temperature monitoring.
That decision should be made before quotation because it affects the test plan, laboratory arrangement and commercial scope.
The FAT document package should clearly distinguish between:
- tests performed on the ordered unit;
- existing type-test reports;
- calculated thermal design information;
- temperature controller functional checks;
- optional project-specific thermal tests.

What Should Engineers Investigate When One Phase Runs Hotter?
A higher temperature reading on one phase does not automatically prove a winding defect.
Start by comparing the operating conditions.
Check:
- phase currents;
- load imbalance;
- harmonic current;
- ambient temperature;
- fan status;
- cooling-air obstruction;
- dust contamination;
- enclosure ventilation;
- sensor location and calibration;
- terminal and connection heating.
Temperature trends are usually more useful than a single isolated reading.
If one phase temperature increases while load, ambient conditions and cooling remain unchanged, further inspection is justified.
Infrared thermography can help identify surface heating and connection problems, while internal winding diagnosis may require additional analysis.

Hot-Spot Temperature Should Be Considered During Transformer Selection, Not Only After Installation
Temperature monitoring cannot correct a transformer that was thermally mis-specified.
The most effective hot-spot control begins with transformer design and project input data.
For EPC and industrial projects, verify the relationship between:
load profile → losses → airflow → winding temperature distribution → insulation thermal stress
before approving the transformer specification.
This is especially relevant where the project includes:
- frequent peak loading;
- high ambient temperature;
- restricted transformer rooms;
- high-IP enclosures;
- forced-air dependence;
- significant harmonics;
- high altitude;
- limited maintenance access.
IEC 60076-11:2018 specifically recognizes issues such as enclosure performance and thermal effects associated with altitude within the dry-type transformer standard framework.
FAQ
1. What is the hot-spot temperature of a dry-type transformer?
It is the temperature at the locally hottest thermally stressed point of the transformer, usually associated with the winding or another current-carrying region. It can be higher than the average winding temperature.
2. Is hot-spot temperature the same as winding temperature rise?
No. Average winding temperature rise represents an average thermal condition. The hot spot represents the highest local temperature. The relationship depends on transformer design, cooling and operating conditions.
3. Can Pt100 sensors measure the actual transformer hot spot?
They measure temperature at the installed sensor location. If the sensor is not located at the actual hottest point, its reading should not automatically be treated as the true winding hot spot.
4. Can infrared thermography identify an internal winding hot spot?
Infrared thermography is very useful for accessible surface temperatures and abnormal thermal patterns, but it cannot directly see every internal conductor location inside a cast winding.
5. Does a transformer operating below rated kVA always have a safe hot-spot temperature?
No. Ambient temperature, enclosure ventilation, harmonics, airflow restrictions, phase imbalance and cooling system condition can affect thermal performance.
6. Should temperature-rise testing be included in every transformer FAT?
Not automatically. The required test scope should distinguish routine, type and special/project-specific testing. Temperature-rise requirements should be agreed before quotation.
7. What thermal information should be included in a dry-type transformer RFQ?
Provide rated capacity, voltages, frequency, load profile, expected overloads, ambient conditions, altitude, enclosure, cooling method, harmonic information where relevant, insulation requirements and temperature-monitoring expectations.
CTA
If you are preparing a dry-type transformer RFQ for a thermally demanding project, provide the rated capacity, primary and secondary voltage, load profile, ambient temperature, altitude, enclosure/IP requirement, cooling method and harmonic information where applicable.
The transformer thermal design, temperature monitoring arrangement and required test scope can then be reviewed before the technical datasheet and quotation are finalized.