Dry-Type Transformer: Operation, Cooling & Losses

2026-08-14

During transformer commissioning, an overheating alarm does not automatically mean the transformer is undersized.

A transformer may have the correct rated kVA, primary voltage and secondary voltage while still operating at an unexpectedly high temperature.

Restricted ventilation, high ambient temperature, harmonic loads, incorrect system frequency, enclosure design or sustained overvoltage can all affect operating temperature.

That is why understanding the dry type transformer working principle has practical value for EPC contractors and procurement teams.

The useful questions are not simply, “What is electromagnetic induction?”

The questions are:

Why does the transformer heat up?

Why does 50 Hz versus 60 Hz matter?

Why can two transformers with the same kVA rating behave differently?

When is forced-air cooling required?

What information must be sent to the manufacturer before production?

Those questions connect transformer theory directly with project risk.

1.webp

How Power Moves Through a Dry Type Transformer

Consider an 11 kV/400 V three-phase dry type transformer.

When AC voltage is applied to the primary winding, alternating current establishes a changing magnetic field.

The transformer core provides the main magnetic path.

The resulting alternating magnetic flux links both the primary and secondary winding, inducing voltage in the secondary circuit.

The primary and secondary circuits normally transfer energy through magnetic coupling rather than a direct conductive connection.

This is the practical foundation of electromagnetic induction in transformers.

The Transformer Core Is Part of the Electrical Design

The core is not simply a mechanical frame supporting the coils.

It determines the magnetic path through which alternating flux travels.

Its design affects:

  • magnetic flux density;
  • excitation current;
  • no-load loss;
  • acoustic noise;
  • operating temperature;
  • overall transformer performance.

If magnetic flux density is pushed too high, the core can operate closer to saturation, potentially increasing excitation current, losses and noise.

This is one reason two transformers carrying the same nameplate rating can have different internal designs and operating characteristics.

2.webp

How the Windings Determine Voltage

A central part of how a dry type transformer works is the relationship between winding turns.

The primary-to-secondary voltage ratio is primarily established by the turns ratio.

An 11 kV/400 V transformer therefore requires a winding ratio corresponding approximately to that voltage relationship.

A manufacturer, however, does not design the winding from turns ratio alone.

The engineering calculation must also consider:

rated frequency, core cross-section, magnetic flux density, conductor current density, insulation clearance, temperature rise, short-circuit forces and tap requirements.

For this reason, an RFQ saying only:

“1000 kVA dry transformer, please quote”

does not contain enough information for a controlled engineering selection.

Why 50 Hz and 60 Hz Matter

Frequency is one of the most frequently overlooked specifications in export enquiries.

Customers sometimes ask whether a 60 Hz transformer can simply be operated at 50 Hz.

The frequency is directly related to the magnetic design.

Operating equipment designed for a different frequency under unchanged voltage conditions can change the core flux level.

The manufacturer therefore needs the actual:Rated Frequency,before confirming the transformer design.

For international projects, a useful technical specification should identify:Primary Voltage,Secondary Voltage,Frequency,Phase,Vector Group,Tap Range,Earthing Arrangement.

These details are much cheaper to correct before manufacturing than after the transformer reaches site.

3.webp

How Can a Dry Type Transformer Operate Without Insulating Oil?

This is where a cast resin transformer differs most visibly from an oil-filled unit.

In common cast-resin designs, the high-voltage winding uses a solid insulation system instead of being immersed in transformer oil.

The key engineering difference is therefore not simply the absence of an oil tank.

The insulation and heat-transfer paths are different.

An oil-immersed transformer uses insulating liquid as part of both its dielectric and thermal management system.

A dry type transformer insulation system relies primarily on solid insulation together with surrounding air for heat dissipation.

Air passages around the coils therefore become part of the thermal design.

Where Does Transformer Heat Come From?

A transformer has no high-speed rotating mechanism, but it still produces losses.

One component is no-load loss.

This is mainly associated with the energized magnetic core and exists whenever the transformer is energized, even when the secondary load is very small.

The other major component is load loss.

Winding resistance produces I²R loss, so winding-related heating increases significantly as current rises.

This is why transformer loading cannot be evaluated from kW consumption alone.

Load current, harmonics, ambient temperature and cooling conditions all influence dry type transformer temperature rise.

4.webp

How Does a Dry Type Transformer Cool Itself?

The dry type transformer cooling system can be understood as an air heat-transfer path.

Heat generated in conductors and the core moves toward the coil and structural surfaces.

Surrounding air then carries that heat away.

Two cooling designations frequently encountered are:

AN – Air Natural

Natural air circulation provides cooling.

AF – Air Forced

Fans increase airflow through the transformer.

A common procurement mistake is to assume that adding fans automatically allows continuous transformer overload.

It does not.

Any AF rating should be supported by the manufacturer's thermal design.

Coil geometry, ventilation ducts, fan arrangement and temperature-control system must work together.

Engineering Application 1: Indoor Building Substation

Consider an 11/0.4 kV dry type distribution transformer installed in the basement electrical room of a hospital, commercial building or data center.

The buyer may initially focus on the advantages of avoiding a liquid-filled transformer indoors.

During operation, ventilation often becomes the more immediate issue.

If the transformer room has inadequate air inlet and exhaust capacity, heated air can recirculate around the transformer.

The effective ambient temperature around the windings then becomes higher than the outdoor ambient temperature.

An EPC contractor should therefore evaluate:

transformer-room ventilation, spacing between transformers, distance from walls, enclosure ventilation and cable routing.

The transformer and the room ventilation system should be treated as one thermal system.

Engineering Application 2: Factory Loads with VFDs

Now consider an industrial plant where an 11 kV/415 V transformer supplies motors, variable-frequency drives, UPS systems and rectifier loads.

These are not always ideal linear loads.

Higher harmonic content can increase certain transformer losses and heating effects.

When a project includes a large concentration of VFDs or other nonlinear loads, the RFQ should state:

Load Type

and provide harmonic information when available.

Do not wait until the transformer is manufactured before disclosing the actual load profile.

5.webp

Dry Type Transformer vs Oil Immersed Transformer

The fundamental electromagnetic principle is similar.

Both transfer energy between windings through alternating magnetic flux in a magnetic core.

The major practical difference lies in the transformer insulation and cooling system.

A dry type transformer primarily uses solid insulation and air cooling.

An oil immersed transformer uses insulating liquid for dielectric insulation and heat transfer.

This produces different engineering strengths.

Indoor buildings, hospitals, commercial facilities and similar installations frequently consider dry-type equipment.

Outdoor substations, utility networks and higher-capacity applications frequently use oil-immersed designs.

The decision should not be reduced to which technology is “better.”

Installation location, fire requirements, capacity, voltage, environment, lifecycle strategy and project budget all matter.

Procurement Risk: An Incomplete RFQ

One of the largest risks in an international transformer project occurs before production starts.

The specification is incomplete.

A controlled RFQ should normally identify:Rated Power,Primary Voltage,Secondary Voltage,Frequency,Vector Group,Tap Range,Impedance,Cooling Method,Installation Environment

Altitude,Enclosure / IP Requirement,Applicable Standard.

Altitude deserves special attention because air insulation and cooling conditions change with installation elevation.

The current IEC dry-type transformer standard is IEC 60076-11:2018, whose scope covers specified dry-type power transformers and extends to equipment having a highest voltage up to 72.5 kV.

If the transformer will operate at 2,000 m, 3,000 m or another high-altitude site, that information should appear in the RFQ rather than after the transformer is built.

Voltage Matching in Export Projects

Export transformers encounter a wide range of power systems.

Examples include:10 kV,11 kV13.8 kV,20 kV,22 kV, 33 kV

with secondary systems such as:400 V,415 V,440 V,480 V.

A buyer should never provide only the destination country and ask the manufacturer to assume the operating voltage.

Several voltage systems can exist within the same country.

The preferred input is the actual system voltage, together with the required insulation level and system details.

For replacement projects, the existing transformer nameplate and single-line diagram are extremely useful.

What Should Be Checked During FAT?

A dry type transformer FAT test should be more than a visual inspection and energization demonstration.

The factory should complete the routine tests required by the agreed standard and project specification and provide the relevant records.

Depending on the project, the FAT package may include verification of:

  • winding resistance;
  • voltage ratio;
  • vector group and phase displacement;
  • short-circuit impedance;
  • load loss;
  • no-load loss;
  • no-load current;
  • applied-voltage withstand;
  • induced-voltage withstand;
  • insulation-related performance;
  • temperature-monitoring functions.

Type tests or special tests may also be required by the contract.

For IEC-based projects, IEC 60076-11 remains the dedicated IEC standard for dry-type power transformers, while the wider IEC 60076 series covers other transformer requirements.

Before issuing the purchase order, the buyer should define:

Which tests are required?

Which tests require third-party involvement?

Will the customer witness FAT?

Which reports must ship with the transformer?

Adding these requirements after manufacturing is a common source of delay and additional cost.

Export Packaging Is Part of Transformer Delivery

Passing FAT does not end the engineering responsibility.

An export transformer may undergo:factory lifting;truck transportation;port handling;ocean shipment;destination-port handling;site transportation.

The packaging system therefore needs to protect the transformer from moisture, dust, mechanical movement and vulnerable impact points.

Depending on the shipment, an export packing plan may include:moisture protection;mechanical fixing;protected HV/LV terminals;separately packed accessories;lifting marks;

shipping marks;wooden cases where required.

For larger units, the supplier and buyer should also confirm whether the enclosure, cooling fans or other accessories will be removed for shipment.

A transformer that passes FAT but arrives with damaged terminals or displaced accessories is still a failed delivery from the buyer's perspective.

6.webp

Using the Working Principle to Make a Better Selection

Understanding the dry type transformer working principle explained above makes procurement decisions more logical.

High load current means load loss and temperature rise deserve attention.

High ambient temperature means the cooling margin must be reviewed.

High altitude affects air insulation and cooling.

Heavy VFD loading means harmonics should be considered.

A small transformer room requires ventilation analysis.

Outdoor installation requires a suitable enclosure and environmental design.

The correct purchasing question is therefore not:

“Do you have a standard 1000 kVA transformer?”

It is:

“Can this 1000 kVA transformer operate correctly in my actual electrical system and installation environment?”

FAQ

1. Does a dry type transformer contain any oil?

Common cast resin dry type transformers do not depend on transformer oil for their principal insulation and cooling system. The exact construction should still be confirmed from the manufacturer's design.

2. Why does a dry type transformer become hot?

Heat mainly comes from transformer losses, including core-related no-load losses and current-related load losses.

3. Does every dry type transformer require cooling fans?

No. Many transformers operate under AN cooling, while some designs also provide AF cooling capability.

4. Can a 50 Hz transformer operate on 60 Hz?

The manufacturer should verify the design conditions. Frequency affects magnetic operation, so compatibility should not be judged from voltage and kVA alone.

5. Can dry type transformers be installed outdoors?

Yes, when the transformer and enclosure are designed for the required outdoor environment, protection level, ventilation and weather exposure.

6. Why must altitude be stated?

Altitude affects air insulation and cooling performance. High-altitude applications should therefore be identified during design.

7. Can customers witness the FAT?

Yes. A FAT witness test can be arranged when it is included in the project requirements and coordinated with the production schedule.

8. Is a dry type transformer more efficient than an oil transformer?

Not automatically. Compare the actual no-load losses, load losses and expected operating profile of the specific transformer designs.

9. What information should be included in a dry transformer RFQ?

At minimum: rated power, primary and secondary voltage, frequency, phase, vector group, tap range, impedance, installation environment, altitude, applicable standard and enclosure requirements.

10. Which IEC standard applies to dry type transformers?

IEC-based projects commonly reference the IEC 60076 series, with IEC 60076-11 specifically covering dry-type power transformers within its defined scope.

Call To Action

If you are preparing a new dry type transformer project, do not send only kVA and voltage.

Provide the rated capacity, primary and secondary voltage, frequency, vector group, impedance, tap range, ambient conditions, altitude, installation location, enclosure requirement and applicable standard.

Huamei Electrical can review your single-line diagram, transformer specification or existing transformer nameplate and confirm the proposed transformer configuration, FAT requirements, export packaging and delivery arrangement.

Send your transformer specification for technical review and quotation.