F Class vs H Class Dry Type Transformer Insulation
F Class vs H Class Insulation: How to Specify a Dry-Type Transformer
For an EPC specification, F class vs H class dry type transformer insulation should not be treated as a simple choice between a “standard” and a “better” transformer.
Class F and Class H describe the thermal capability of an electrical insulation system. They do not by themselves define transformer efficiency, overload capacity, service life, permissible ambient temperature or acceptable winding temperature during operation.
Under IEC thermal classification, Class F corresponds to thermal class 155°C and Class H to thermal class 180°C. IEC 60076-11 then connects the insulation system thermal class with applicable dry-type transformer temperature-rise requirements.
The practical selection question is therefore not:
“Is H better than F?”
It is:
“What thermal class and temperature-rise design are required for this transformer’s actual load profile, ambient conditions, enclosure, cooling method and expected operating margin?”
That distinction should be resolved before a transformer quotation is commercially compared.
What Do Class F and Class H Actually Mean?
IEC 60085 provides the framework for the thermal evaluation and designation of electrical insulating materials and complete electrical insulation systems.
For the classes relevant here:
| Thermal Class | Letter Designation | Thermal Class Temperature |
|---|---|---|
| 155 | F | 155°C |
| 180 | H | 180°C |
IEC 60085 distinguishes the classification of individual insulating materials from the classification of an electrical insulation system. A transformer winding contains more than one material, so procurement should focus on the insulation system thermal class, rather than assuming that one resin, paper or film determines the rating of the complete transformer.
Materials used in dry-type transformer insulation can include epoxy systems, conductor insulation, films, laminates, aramid papers, glass-fibre materials, spacers and structural insulation components.
For example, Hitachi Energy identifies DMD-based insulation for Class F 155°C applications and NMN-based insulation for Class H 180°C applications. The final thermal classification, however, belongs to the qualified insulation system used in the transformer design rather than to a generic material name alone.
Do Not Confuse Thermal Class F with Fire Behaviour Class F1
This point deserves explicit wording in international RFQs.
“Class F insulation” normally refers to thermal class 155.
“F1,” where specified under the applicable dry-type transformer classification framework, refers to fire behaviour.
They describe different properties.
A specification saying only:
F Class transformer
may therefore be less precise than:
Insulation system thermal class: 155 (F), according to the applicable IEC requirements.
Fire-behaviour requirements should be stated separately.
F Class 155°C vs H Class 180°C: The Basic Difference
The headline difference is 25°C in thermal class designation.
Class F: 155°C
Class H: 180°C
That 25°C difference represents additional thermal capability of the insulation system.
It does not mean that a Class H transformer should normally operate 25°C hotter than an equivalent Class F transformer.
A designer can use the higher thermal capability in different ways.
It may provide additional thermal margin.
It may support a design intended for more demanding ambient conditions.
It may be part of a transformer designed for a higher permissible winding temperature rise.
It may support a particular load duty.
It may also allow a manufacturer to optimize the physical transformer design differently.
The buyer therefore needs the complete thermal design basis, not only the letter H.
Insulation Class and Temperature Rise Are Different Specifications
This is the most important distinction in the entire selection process.
Insulation class defines thermal capability.
Temperature rise defines how much the winding temperature increases above the cooling-air temperature under specified operating and test conditions.
IEC 60076-11:2018 gives the following average winding temperature-rise limits at rated current for these two thermal classes:
| Insulation System Thermal Class | Average Winding Temperature-Rise Limit |
|---|---|
| 155 (F) | 100 K |
| 180 (H) | 125 K |
These figures must not be converted into a simplistic operating rule.
A Class F transformer is not required to operate with a 100 K temperature rise.
A Class H transformer is not required to operate with a 125 K temperature rise.
A project can specify or a manufacturer can design for a lower temperature rise.
This distinction matters because two quotations may both state:
Insulation Class H
while one transformer is designed with substantially more thermal margin than the other.
The RFQ should therefore ask for at least two separate entries:
Insulation system thermal class: ___
Guaranteed / specified winding temperature rise: ___ K
Do not merge them into one parameter..
Why a Class H Transformer Is Not Automatically Better
The higher thermal classification can be technically valuable, but Class H insulation does not independently prove a superior transformer.
It does not automatically guarantee lower no-load loss.
It does not automatically guarantee lower load loss.
It does not automatically guarantee higher efficiency.
It does not automatically guarantee a longer service life.
It does not automatically permit continuous overload.
It does not correct insufficient transformer-room ventilation.
It does not compensate for excessive harmonic loading.
It does not establish the required enclosure rating.
It does not define dielectric insulation level.
For example, a Class H transformer designed to operate close to its thermal capability can have less unused thermal margin than a conservatively designed transformer operating at a substantially lower winding temperature.
The useful engineering parameter is therefore not the insulation class in isolation.
It is the combination of:
thermal class + temperature rise + ambient temperature + load profile + cooling method + enclosure + installation conditions.
When Is Class F Usually a Rational Choice?
Class F remains widely used in cast-resin dry-type transformer applications.
Schneider Electric, for example, identifies Class F as the insulation temperature class used for its Trihal cast-resin transformer system, while its published comparison identifies 155°C for Class F and 180°C for Class H.
Class F can be a technically rational selection where:
-
the transformer operates under normal or controlled ambient conditions;
-
continuous loading is within the transformer’s thermal design;
-
the electrical room has adequate ventilation;
-
AN cooling is sufficient for normal duty;
-
harmonic loading is not unusually severe;
-
the enclosure does not create an unverified airflow restriction;
-
the project does not require a higher thermal class;
-
the specified temperature rise provides adequate margin.
A lower thermal class should not be interpreted as poor quality when the transformer is correctly engineered for the duty.
The objective is to meet the project thermal requirements with controlled ageing and adequate design margin.
When Should Class H Be Evaluated?
Class H deserves serious consideration when the project imposes more demanding thermal conditions.
Examples include:
High Ambient Temperature
If the transformer room is expected to operate above normal reference conditions for extended periods, the manufacturer needs the actual maximum and average cooling-air temperatures.
Simply changing “F” to “H” on the datasheet is not enough.
The thermal design should be reviewed for the declared ambient condition according to the applicable IEC requirements and approved project specification.
Sustained High Loading
A facility operating continuously near transformer rated capacity may have less thermal reserve than a commercial building with a lower average load factor.
Class H may provide useful design flexibility, but transformer loading still has to be evaluated against actual temperature, duration, cooling and manufacturer limits.
For repeated peak loads, the project should separately review dry-type transformer overload capability rather than assuming that Class H equals an automatic overload percentage.
Restricted Enclosure Cooling
Dry-type transformer thermal performance depends on airflow.
A protective enclosure can change that airflow.
Higher IP requirements, screens, filters, restricted louvres or compact electrical rooms can affect cooling.
The insulation class should therefore be reviewed together with the enclosure and the rating of the complete assembled transformer.
Harmonic-Rich Loads
UPS systems, rectifiers, VFDs, data-centre power supplies and other nonlinear equipment can increase transformer heating.
Higher insulation class is not the first correction for an unsuitable harmonic design.
The manufacturer should receive the load type and, where available, harmonic data so additional losses can be evaluated.
Limited Thermal Reserve Is a Project Risk
A project may deliberately specify a higher insulation thermal class together with a lower actual temperature rise.
That approach can create thermal headroom.
However, it must appear clearly in the technical specification.
“Class H” alone does not prove that the manufacturer has used that additional capability as reserve rather than as part of the normal design operating range.
Engineering Scenario 1: Indoor Commercial Distribution
Consider an indicative project:
1250 kVA
11 kV / 415 V
50 Hz
Dyn11
Indoor installation
AN cooling
Ventilated transformer room
Moderate continuous loading
Suppose the site temperature remains within the approved design conditions and the load profile does not contain severe harmonic content or long-duration overload.
The procurement team may receive one quotation with Class F insulation and another with Class H.
Selecting Class H only because 180°C is numerically higher would be weak engineering.
The comparison should instead ask:
What winding temperature rise is guaranteed?
What losses are guaranteed?
What ambient conditions are assumed?
What enclosure is fitted?
What is the AN rated capacity?
What insulation system is offered?
What temperature-rise evidence is available?
If the Class F design already meets the required thermal performance with appropriate margin, changing to Class H may provide little project benefit.
Engineering Scenario 2: Hot Industrial Plant
Now consider:
1600 kVA
11 kV / 415 V
50 Hz
Dyn11
Indoor industrial installation
high summer room temperature
high continuous production load
significant VFD load
metal enclosure
Here, thermal design becomes more demanding.
The engineer should review:
maximum cooling-air temperature;
average ambient temperature;
harmonic spectrum or THDi where available;
continuous and peak loading;
AN and any AF rating;
enclosure airflow;
transformer losses;
room heat rejection;
temperature monitoring;
required temperature-rise limit;
insulation system thermal class.
Class H may form part of a suitable solution.
But specifying Class H while ignoring ventilation, harmonic losses and load profile simply moves attention away from the real thermal problem.
A higher thermal class is a design tool, not a substitute for thermal engineering.
Does Class H Give More Overload Capacity?
Not by itself.
This is a common purchasing mistake.
Overload capability depends on much more than the insulation letter.
Relevant factors include:
-
initial transformer loading;
-
overload magnitude;
-
overload duration;
-
ambient temperature;
-
winding temperature;
-
cooling availability;
-
AN or AF configuration;
-
harmonic losses;
-
enclosure conditions;
-
previous thermal history;
-
manufacturer thermal design.
A transformer using Class H insulation may be designed with greater thermal capability, but the buyer should never convert that into an assumed overload percentage without manufacturer confirmation.
If peak duty is important, the RFQ should state the normal continuous load, maximum peak load, peak duration and frequency.
Insulation Class Does Not Define Dielectric Insulation Level
“Insulation class” can create another procurement ambiguity.
F and H are thermal classifications.
They are not the same as the transformer’s dielectric insulation level.
For a medium-voltage dry-type transformer, the project still needs to define or approve the electrical insulation requirements associated with the system voltage and applicable IEC specification.
For example, an 11 kV transformer specification may need coordination of:
rated winding voltage;
highest voltage for equipment;
applicable dielectric withstand requirements;
system earthing;
project insulation coordination.
Changing thermal class from F to H does not change these electrical system parameters automatically.
What Should Be Written in the RFQ?
For a project where insulation class matters, avoid writing only:
1600 kVA dry-type transformer, Class H.
A more useful RFQ should identify:
Rated capacity
Primary voltage
Secondary voltage
Frequency
Phase
Vector group
Tap range
Impedance
Insulation system thermal class
Required winding temperature rise
Maximum ambient temperature
Average ambient condition where required
Altitude
AN or AF cooling
Normal continuous load
Peak load and duration
Major harmonic-producing loads
Required enclosure / IP rating
Temperature sensors
Temperature controller functions
Fan-control requirement
Alarm and trip interfaces
Applicable IEC standard
Required FAT and documentation scope
This gives suppliers the same engineering basis.
Without it, one manufacturer may quote a conservatively rated transformer while another uses more of the available thermal capability.
The commercial comparison then becomes misleading.
What Should Be Checked in the Technical Datasheet?
Before technical approval, check whether the following values are stated consistently:
| Parameter | What to Verify |
|---|---|
| Insulation system | F / 155°C or H / 180°C |
| Temperature rise | Stated separately from thermal class |
| Rated capacity | Confirm AN and AF ratings separately where applicable |
| Ambient condition | Matches the project |
| Altitude | Matches the site |
| Cooling | AN / AF and operating basis |
| Enclosure | Complete transformer rating with enclosure fitted |
| Monitoring | PT100 or specified temperature sensors |
| Controller | Fan, alarm and trip functions |
| Losses | Guaranteed project values |
| Standard | Applicable IEC/project specification |
The approved technical datasheet, GA drawing and final nameplate information should not contradict each other.
FAT: What Can Be Verified?
A FAT should not be treated as a single test proving that the transformer is “Class H.”
The insulation thermal class is part of the transformer design and insulation-system specification.
During technical document review and FAT, the purchaser can verify:
declared insulation thermal class;
approved technical datasheet;
material or design documentation where contractually required;
temperature-rise requirement;
nameplate information;
temperature-sensor arrangement;
temperature-controller operation;
fan operation for AF configurations;
alarm and trip functions;
consistency with approved drawings.
Temperature-rise testing should be specified and evaluated according to the applicable IEC standard and agreed project test programme rather than assumed to be a routine test repeated on every transformer.
The same principle applies to other type or special test requirements.
Define the required evidence before production.
F Class vs H Class Dry Type Transformer: Selection Summary
| Selection Question | Class F | Class H |
|---|---|---|
| IEC thermal designation | 155°C | 180°C |
| IEC 60076-11 average winding rise limit | 100 K | 125 K |
| Thermal capability | Lower | Higher |
| Suitable for normal dry-type applications | Frequently | Yes |
| Potential value in demanding thermal conditions | Moderate | Higher |
| Automatically improves efficiency | No | No |
| Automatically increases overload capacity | No | No |
| Automatically extends transformer life | No | No |
| Replaces ventilation design | No | No |
| Defines dielectric insulation level | No | No |
| Should be specified together with temperature rise | Yes | Yes |
The correct specification is not simply:
F or H?
It is:
What insulation-system thermal class and guaranteed winding temperature rise provide the required thermal margin under the actual project conditions?
FAQ
1. What is Class F insulation in a dry-type transformer?
Class F refers to thermal class 155°C under IEC thermal classification. It describes the thermal capability of the electrical insulation system and should not be confused with the transformer’s operating temperature or dielectric insulation level.
2. What is Class H insulation in a dry-type transformer?
Class H corresponds to thermal class 180°C. It provides higher thermal capability than Class F, but the actual transformer rating still depends on its complete thermal design, cooling conditions and specified temperature rise.
3. What is the temperature-rise limit for Class F dry-type transformers?
IEC 60076-11:2018 identifies a 100 K average winding temperature-rise limit at rated current for thermal class 155 (F). A transformer may be specified or designed for a lower rise.
4. What is the temperature-rise limit for Class H?
IEC 60076-11:2018 identifies 125 K for thermal class 180 (H). This should not be interpreted as a requirement to operate the winding at that rise during normal service.
5. Is Class H always better than Class F?
No. Class H has a higher thermal classification, but transformer performance depends on temperature rise, losses, load profile, ambient temperature, ventilation, enclosure, harmonics and design margin.
6. Does Class H mean the transformer can be continuously overloaded?
No. Continuous or short-term overload capability must be confirmed from the transformer thermal design, loading conditions, cooling configuration and manufacturer data.
7. Can I specify Class H insulation with a lower temperature rise?
Yes, subject to the transformer design and project specification. Separating the insulation thermal class from the required temperature rise is often the clearest way to define the intended thermal margin.
8. What should I send a supplier before selecting F or H?
Provide capacity, primary and secondary voltage, load profile, ambient temperature, altitude, enclosure, cooling method, harmonic information where relevant, required temperature rise, applicable standard and project operating conditions.
CTA — Request a Thermal Specification Review
If you are preparing a dry-type transformer RFQ, provide the rated capacity, primary and secondary voltage, vector group, impedance, required insulation thermal class, winding temperature-rise requirement, maximum ambient temperature, altitude, cooling method, enclosure, load profile, quantity and destination country.
For projects with high ambient temperature, harmonic loads or repeated peak loading, include the available load and site-condition data so the transformer thermal specification can be reviewed before quotation.