Leave Your Message

SG(B)13 10kV Non-Encapsulated Dry-Type Transformer

The SG(B)13 10kV non-encapsulated dry-type transformer uses vacuum pressure impregnation (VPI) to treat its windings. Its open-ventilated structure supports heat dissipation. The insulation system is generally Class H, with an insulation-system temperature of 180°C, a reference temperature of 145°C, and a winding temperature rise of 125 K. Final ratings and configurations are subject to the approved technical specification.

  • Product Model SG(B)13-10kV
  • Transformer Type Non-Encapsulated Dry-Type
  • Rated Capacity 30–1600 kVA
  • Rated High Voltage 6 / 6.3 / 10 / 10.5 / 11 kV
  • Rated Low Voltage 0.4 kV
  • Number of Phases Three Phase
  • Insulation Class Class H
  • Insulation System Temperature 180°C
  • Reference Temperature 145°C
  • Winding Temperature Rise 125 K
  • Winding Process Vacuum Pressure Impregnation
  • Winding Structure Non-Encapsulated
  • Vector Group Yyn0 / Dyn11
  • Load Loss (75°C) 80–1,170 W
  • No-load Loss Yyn0: 600–14,500 W; Dyn11: 630–14,500 W
  • No-load Current 0.5–1.7%
  • Short-circuit Impedance 4.0% (30–500 kVA); 4.5% (630–1,600 kVA)

Product features

This series of transformers takes safety and reliability as the core design principles, integrating high-performance insulating materials, sophisticated coil structures and advanced manufacturing processes. It can stably operate in complex and harsh working environments, and is widely trusted in fields with high safety and stability requirements. The following is a detailed elaboration on its excellent safety performance and high reliability:
1.Good Safety Performance: The transformer adopts high-quality environmentally friendly insulating materials, which are carefully selected and strictly tested to ensure that the content of combustible components is minimized. These insulating materials have multiple safety characteristics such as non-toxicity, self-extinguishing, flame retardancy and fire resistance, fully complying with international environmental protection and safety standards. In the event of accidental open fire combustion, the insulating materials will not release toxic or harmful gases, and the smoke production is almost negligible, effectively avoiding secondary hazards such as air pollution and personnel poisoning caused by smoke and toxic gases.
2.This outstanding safety performance makes the transformer particularly suitable for key areas with high fire protection requirements and large load demands. Typical application scenarios include high-rise buildings, where the dense population and complex pipeline layout put forward strict requirements on fire safety; airports and subways, which are important transportation hubs with large passenger flow and high reliability requirements; metallurgy and petrochemical industries, where the working environment is harsh and flammable and explosive substances are present, requiring equipment to have excellent flame retardancy and explosion-proof performance; as well as large shopping malls, hospitals and other public places with high pedestrian flow and high fire safety standards. In these scenarios, the transformer can effectively reduce fire risks and ensure the safety of personnel and property.
3.The core manufacturing process adopts vacuum pressure-impregnation technology. The windings are subjected to strict vacuum pressure-impregnation and curing treatment, which ensures that the insulating material can fully penetrate into every gap of the winding, eliminating air bubbles and moisture in the insulation layer. This not only improves the insulation strength of the winding, but also enhances the bonding force between the conductor and the insulating material, forming a solid integral structure. In addition, the coil compression adopts a pressure block structure, which applies uniform pressure to the coil, ensuring that the winding remains compact and stable during long-term operation, and avoiding insulation degradation caused by coil loosening.
4.Thanks to the above structural design and manufacturing process, the transformer has an extremely low partial discharge level (stably controlled below 5pC), which can effectively reduce insulation aging caused by partial discharge and prolong the service life of the equipment. During the entire service cycle, the transformer has no risks of cracking, insulation degradation or other common faults, and can maintain stable and reliable operation even under long-term full-load or intermittent operation conditions, reducing the frequency of maintenance and downtime and ensuring the continuous and stable operation of the power supply system

Product Specifications

rated capacity(KVA) connection group lable voltage combination(KV) no-load current(%) load loss(W) no-load loss(W) short-circuit impedance(%)
High voltage(H.V.) H.L.tap range (L.V.)
30 Dyn11 Yyn0 6
6.3
6.6
10
10.5
11
±5% ±2×2.5% 0.4 2.00 760 190 4.0
50 2.00 1070 270
80 1.50 1480 370
100 1.50 1690 400
125 1.30 1980 470
160 1.30 2280 540
200 1.10 2710 620
250 1.10 2960 720
315 1.00 3730 880
400 1.00 4280 980
500 1.00 5230 1160
630 0.85 6290 1340
630 0.85 6400 1300 6.0
800 0.85 7460 1520
1000 0.85 8760 1770
1250 0.85 10300 2090
1600 0.85 12500 2450
2000 0.70 15500 3050
2500 0.70 18400 3600
1600 0.85 13900 2450 8.0
2000 0.70 17100 3050
2500 0.70 20200 3600

detail pictures

SGB13-10KV (1)
SGB13-10KV (2)
SGB13-10KV (3)
SGB13-10KV (4)
SGB13-10KV (5)
SGB13-10KV (6)
SGB13-10KV (7)
SGB13-10KV (8)

FAQ

Send us your required capacity, primary/secondary voltage, frequency and application. Our engineering team will help you select the appropriate transformer configuration.
GET TECHNICAL SUPPORT