Leave Your Message

China Factory Suppliers for 10kV Prefabricated Substation: Compact Outdoor Power Distribution Solution

In both urban and rural power distribution environments, the YB-12 outdoor pre-assembled substation (European style) stands out for its exceptional adaptability. This compact solution seamlessly integrates comprehensive power distribution functions, significantly minimizing floor space and reducing both construction and land costs. Manufactured in China, this innovative substation from reliable suppliers offers support for ring network, dual power supply, and radial wiring configurations. Its stable operation, easy maintenance, and flexibility for relocation make it an ideal choice for modernizing power distribution networks. As a key piece of technical equipment, the YB-12 substation plays a crucial role in enhancing efficiency and reliability in power distribution, making it a top selection from our factory

    Flexible grid connection and system compatibility capabilities

    1. Complete ring network solution

    Configurable fully insulated and fully sealed ring network cabinet units, enabling advanced power supply modes such as dual-ring network and single-ring network. Each unit is connected through prefabricated cables, forming a complete ring network system. In the event of a fault in any section of the line, it can be quickly isolated and power restored, with power reliability reaching 99.99%.

    2. Dual power automatic switching system

    It can provide a complete dual power access solution for important users, equipped with an automatic transfer switch (ATS) and corresponding protection systems. When the main power supply fails, the backup power can be automatically switched on within an extremely short period of time, ensuring uninterrupted power supply for critical loads such as hospitals, data centers, and important production lines.

    3. Standardized radial terminal configuration

    To meet the radial power supply requirements of ordinary users, an economical and efficient standardized configuration solution is provided. On the high-voltage side, a load switch-fuse combination electrical apparatus can be used to protect the transformer. On the low-voltage side, intelligent frame circuit breakers and molded case circuit breakers are configured to form a complete protection system.

    4. Future-oriented system scalability

    Adopting a modular design concept, standard interfaces are reserved for electrical wiring. When the user's load increases in the future, it can be expanded quickly by replacing the transformer module or increasing the capacity of the low-voltage cabinet module. This design reduces the expansion cost during the product's life cycle by more than 50%.

    Product Specifications

    Name Unit High-voltage electrical cabinet Transformer Low-voltage electrical cabinet
    nominal voltage KV 10 10/0.4 0.4
    rated current A 630 100~2500
    rated frequency Hz 50 50 50
    rated capacity KVA 100~1250
    Rated thermal stability current kA 20/4S 30/15
    Rated dynamic stable current (peak) kA 50 63
    Rated closing short-circuit current (peak) kA 50 15~30
    Rated breaking short-circuit current kA 31.5
    Rated starting load current A 630
    lmin power frequency withstand voltage kA Intergranular 42 fracture surfaces between 48 layers 35/28(5min) 20/2.5
    lightning impulse withstand voltage kA Intergranular 42 fracture surfaces between 48 layers 75
    Shell protection grade IP23 IP23 IP23
    Noise level dB Oil transformer<55、 Dry transformer≤65
    loop number amount 1~6 4~30
    Maximum reactive power compensation on the low-voltage side kvar 300

    Detail Pictures

    Frequently Asked Questions

    What is the power reliability of your ring network solution?
    Our complete ring network solution achieves a power reliability of 99.99%. In the event of a fault in any section of the line, the system quickly isolates the fault and restores power.
    How fast does the dual power automatic switching system operate?
    Equipped with an Automatic Transfer Switch (ATS) and protective systems, it automatically switches to backup power within an extremely short period when the main power supply fails, ensuring uninterrupted operation for critical loads.
    Can the system be expanded as our power load increases?
    Yes, the system features a modular design with reserved standard interfaces. You can easily expand capacity by replacing the transformer module or increasing the low-voltage cabinet capacity, reducing expansion costs by over 50%.
    What is the shell protection grade for the cabinets and transformers?
    The high-voltage electrical cabinet, transformer, and low-voltage electrical cabinet all feature a shell protection grade of IP23.
    What are the noise levels of the transformers?
    The noise level for the oil transformer is less than 55 dB, and for the dry transformer, it is less than or equal to 65 dB.
    What is the maximum reactive power compensation on the low-voltage side?
    The maximum reactive power compensation supported on the low-voltage side is 300 kvar.