China S22-M Oil-Immersed Transformer 35kV 2500kVA Power Transmission - Suppliers & Factory Direct Product
Product Application
Application of High Magnetic Flux Oriented Silicon Steel Sheets
The core magnetic path of the transformer is made of high magnetic permeability oriented silicon steel sheets. Compared with traditional silicon steel sheets, its magnetic permeability is increased by more than 15%, and the iron loss value is reduced by 20% to 30%. This material is processed through a special grain orientation optimization process, which makes the magnetic domains more orderly, effectively reducing the hysteresis loss and eddy current loss during the alternating magnetic field process.
Selection of Environmental-Friendly Insulating Materials
The transformer is equipped with environmentally friendly insulating oil and insulating paper. The insulating oil is made of natural esters or synthetic esters, which are environmentally friendly. Compared to traditional mineral insulating oil, it is biodegradable and will not cause pollution to the soil or water sources if it leaks, thus conforming to the concept of green power development.
High-Strength Metal Structural Components
The structural components such as transformer oil tanks and clamps are made of high-strength cold-rolled steel plates. They are formed through CNC stamping and welding. The yield strength of the material reaches over 345 MPa. Compared with ordinary steel plates, the anti-deformation ability has been enhanced by 40%, effectively resisting external force impacts during transportation and installation.
Full Inclined Joint Stacking Process of the Core
The transformer core adopts the full inclined joint stacking process. Compared with the traditional direct joint process, the magnetic resistance at the joint is reduced by more than 60%, effectively reducing the leakage magnetic loss and noise at the joint. During the stacking process, a special positioning tool is used to ensure the flatness and verticality of the core laminations, and the gap between the laminations is controlled within 0.05mm, ensuring uniform magnetic permeability of the core.
Product Specifications
| Rated Capacity (KVA) | Connection Group Label | Voltage Combination (KV) | No-Load Current (%) | Load Loss (T) | No-Load Loss (T) | Short Circuit Impedance (%) | |||
|---|---|---|---|---|---|---|---|---|---|
| H.V. | Tapping Range | L.V. | DY | Yy | |||||
| 30 | Yyn0 Dyn11 |
10 6.3 6 |
±5% ±2×2.5% |
0.4 | 1.5 | 505 | 480 | 80 | 4.0 |
| 50 | 1.3 | 730 | 695 | 100 | |||||
| 63 | 1.2 | 870 | 830 | 110 | |||||
| 80 | 1.2 | 1050 | 1000 | 130 | |||||
| 100 | 1.1 | 1265 | 1200 | 150 | |||||
| 125 | 1.1 | 1510 | 1440 | 170 | |||||
| 160 | 1.0 | 1850 | 1760 | 200 | |||||
| 200 | 1.0 | 2185 | 2080 | 240 | |||||
| 250 | 0.9 | 2560 | 2440 | 290 | |||||
| 315 | 0.9 | 3065 | 2920 | 340 | |||||
| 400 | 0.8 | 3615 | 3440 | 410 | |||||
| 500 | 0.8 | 4330 | 4120 | 480 | |||||
| 630 | 0.6 | 4960 | 4960 | 570 | 4.5 | ||||
| 800 | 0.6 | 6000 | 6000 | 700 | |||||
| 1000 | 0.6 | 8240 | 8240 | 830 | |||||
| 1250 | 0.5 | 9600 | 9600 | 970 | |||||
| 1600 | 0.5 | 11600 | 11600 | 1170 | |||||
Detail Pictures
Frequently Asked Questions
Q
What are the advantages of using high magnetic flux oriented silicon steel sheets in the S22-M transformer?
High magnetic flux oriented silicon steel sheets increase magnetic permeability by more than 15% and reduce iron loss by 20%–30% compared to traditional silicon steel sheets. The special grain orientation optimization process makes magnetic domains more orderly, effectively minimizing hysteresis loss and eddy current loss during alternating magnetic field operation.
Q
Why are environmentally friendly insulating materials used in this transformer?
The transformer uses natural ester or synthetic ester insulating oil, which is fully biodegradable. Unlike traditional mineral insulating oil, it will not pollute soil or water sources in the event of a leak, making it compliant with modern green power development standards and environmental regulations.
Q
What makes the structural components of the S22-M transformer more durable?
The oil tanks and clamps are manufactured from high-strength cold-rolled steel plates using CNC stamping and welding. With a yield strength exceeding 345 MPa, these components offer 40% greater anti-deformation capability compared to ordinary steel plates, providing reliable protection during transportation and installation.
Q
How does the full inclined joint stacking process improve transformer performance?
The full inclined joint stacking process reduces magnetic resistance at the core joints by more than 60% compared to traditional direct joint methods. This significantly lowers leakage magnetic loss and operational noise. Lamination gaps are precisely controlled within 0.05mm using special positioning tools, ensuring uniform magnetic permeability throughout the core.
Q
What rated capacity range does the S22-M transformer cover?
The S22-M transformer covers a rated capacity range from 30 KVA to 1600 KVA, supporting connection group labels Yyn0 and Dyn11, with high voltage options of 10 kV, 6.3 kV, and 6 kV, and a standard low voltage output of 0.4 kV.
Q
What is the short circuit impedance specification for the S22-M transformer?
The short circuit impedance is 4.0% for rated capacities from 30 KVA to 500 KVA, and 4.5% for capacities from 630 KVA to 1600 KVA. The tapping range supports ±5% or ±2×2.5% voltage adjustment to accommodate varying grid conditions.