China Suppliers Factory: 110kV 10000kVA Outdoor Oil Immersed Power Transformer for Reliable Power Substations
Product Application
Low-noise environmental-friendly design, suitable for various scenarios
Low-noise operation is achieved through structural optimization and process improvement. The core is made using a high-precision stacking process, combined with an elastic clamping structure, which reduces core vibration and magnetic expansion noise. The winding is tightly wound and the size is stabilized through constant pressure drying treatment, thereby reducing electromagnetic vibration noise. A low-noise cooling fan (air-cooled type) is selected. The fan starts and stops automatically based on oil temperature and load, further reducing operating noise.
Compact structure and lightweight design, saving infrastructure costs
Based on the electromagnetic optimization design concept, the structure is streamlined to the greatest extent while ensuring performance. The layout of the engine body and the dimensions of components are optimized, resulting in a 15%–20% reduction in the equipment's volume compared to traditional products, and a corresponding weight reduction, achieving a lightweight design. An integrated structure design is adopted to reduce redundant components and improve space utilization. This not only lowers transportation difficulty and costs but also saves installation area, especially suitable for installation scenarios with limited space such as urban cores, tunnels, and subways.
High-quality insulation configuration, with outstanding electrical performance
Completely use high-quality insulating materials. The insulating components are made of high-strength insulating materials such as high-quality laminated wood and epoxy glass tape, which will not crack or deform even under short-circuit electric force, and can maintain stability.
Highly intelligent and adaptable, meeting the upgrade requirements of the power grid
Deeply integrated into the intelligent power grid construction system, it has a complete intelligent monitoring and control interface, enabling real-time collection and remote transmission of key operating parameters such as oil temperature, oil level, voltage, and current. Equipped with intelligent protection devices, including pressure release valves, temperature controllers, and oil level alarms, when equipment experiences overheating, overpressure, or abnormal oil levels, it can promptly issue alerts and trigger protection actions to prevent the expansion of faults. It supports coordinated operation with new energy power generation systems and energy storage equipment, possesses flexible power regulation and voltage adaptation capabilities, and helps with the grid connection and absorption of distributed energy.
Product Specifications
| Rated Capacity (KVA) | Voltage Combination (KV) | Connection Group Table | No-Load Loss (W) | Load Loss (W) 75° | No-Load Current (%) | Short Circuit Impedance (%) | ||
| H.V. | High-Voltage Tapping Range | L.V. | ||||||
| 2000 | 35 | ±3×2.5% | 6.3 / 10.5 | Yd11 | 2300 | 19240 | 0.8 | 6.5 |
| 2500 | 2720 | 20640 | 0.8 | |||||
| 3150 | 35 / 38.5 | ±3×2.5% | 6.3 / 10.5 | 3230 | 24710 | 0.72 | 7.0 | |
| 4000 | 3870 | 29160 | 0.72 | |||||
| 5000 | 4640 | 34200 | 0.68 | |||||
| 6300 | 5630 | 46770 | 0.68 | 7.5 | ||||
| 8000 | 35 / 38.5 | ±3×2.5% | 6.3 / 6.6 / 10.5 / 11 | Ynd11 | 7870 | 40610 | 0.6 | |
| 10000 | 9280 | 48050 | 0.6 | |||||
| 12500 | 10940 | 56860 | 0.56 | 8.0 | ||||
| 16000 | 13170 | 70320 | 0.54 | |||||
| 20000 | 15570 | 82780 | 0.54 | |||||
Detail Pictures
Frequently Asked Questions
Q
What is the rated capacity range of this oil-immersed transformer?
This oil-immersed transformer is available in rated capacities ranging from 2,000 KVA to 20,000 KVA, covering a wide range of power distribution applications including industrial facilities, urban infrastructure, tunnels, and subways.
Q
What voltage combinations are supported by this transformer?
The transformer supports high-voltage inputs of 35 kV and 38.5 kV, with low-voltage outputs of 6.3 kV, 6.6 kV, 10.5 kV, and 11 kV, with a high-voltage tapping range of ±3×2.5% to accommodate grid voltage fluctuations.
Q
How does the low-noise design work in this transformer?
Low-noise performance is achieved through a high-precision core stacking process, elastic clamping structure to minimize vibration, constant pressure drying of windings to stabilize dimensions, and an auto-start/stop low-noise cooling fan that responds to oil temperature and load conditions.
Q
Is this transformer suitable for space-constrained installation environments?
Yes. The compact and lightweight design reduces equipment volume by 15%–20% compared to traditional products. Its integrated structure minimizes redundant components, making it especially suitable for urban cores, tunnels, subways, and other locations where installation space is limited.
Q
What intelligent monitoring and protection features are included?
The transformer features a complete intelligent monitoring interface for real-time collection and remote transmission of oil temperature, oil level, voltage, and current data. It is equipped with pressure release valves, temperature controllers, and oil level alarms that automatically issue alerts and trigger protective actions in the event of overheating, overpressure, or abnormal oil levels.
Q
Can this transformer be integrated with renewable energy and energy storage systems?
Yes. This transformer supports coordinated operation with new energy power generation systems and energy storage equipment. It offers flexible power regulation and voltage adaptation capabilities, facilitating the grid connection and absorption of distributed energy sources such as solar and wind power.