KYN28-12 Armored Withdrawable AC Metal-Enclosed Switchgear - Top China Suppliers & Factory Solutions
Basic Product Overview
KYN28-12 high-voltage switchgear cabinet (labeled as — feeder cabinet), a mainstream indoor metal-clad switchgear widely used in 10kV power distribution systems. As a core device in medium-voltage power grids, it undertakes the tasks of power receiving, distribution, fault protection, and operational monitoring, and is widely applied in substations, industrial and mining enterprises, commercial buildings, and urban power distribution networks.
The KYN28-12 cabinet (also known as "KYN28A-12") adopts a withdrawable, compartmentalized metal-enclosed structure (complying with GB3906-2020IEC 62271-200). Its design separates the cabinet into independent functional compartments through grounded metal partitions:
- Circuit Breaker Compartment
- Busbar Compartment
- Cable Compartment
- Secondary Control Compartment
This design prevents fault expansion between compartments and improves the safety of operation and maintenance. The cabinet functions as a "feeder cabinet" — responsible for distributing power from the main busbar to downstream equipment or lines — and is marked with the model KYN28-12 (applicable to 12kV systems) on the top panel.
Application Scenarios
The secondary circuit uses plug-in connectors, simplifying wiring and maintenance. As a feeder cabinet, the KYN28-12 is mainly used to distribute power from the main busbar to downstream loads (e.g., transformers, motors, or other distribution cabinets). Typical application scenarios include:
-
Industrial Plants Power distribution for high-power equipment (e.g., pumps, fans, production lines) in steel, chemical, and manufacturing industries.
-
Commercial Buildings Power supply for lighting, air conditioning, and elevators in shopping malls, office buildings, and hospitals.
-
Urban Substations 10kV distribution network outgoing lines, connecting to residential area transformers.
-
Renewable Energy Systems Connecting wind/solar power generation units to the grid (with customized protection functions).
Core Technical Parameters
Adapted to 10kV power systems; maximum operating voltage: 12kV
Matches the standard power grid frequency in most countries and regions
- Main circuit: 630A, 1000A, 1250A, 1600A
- Auxiliary circuit: 220V / 380V
- Short-time withstand: ≥25kA (4s duration)
- Peak withstand: ≥63kA
- Power frequency (1min): 42kV
- Lightning impulse: 75kV
IP54 available for harsh environments
Derating by 1% per 1°C above 40°C Altitude: ≤1000m
Derating required above 1000m Humidity: Daily avg ≤95%, Monthly avg ≤90%
No condensation
Detail Pictures