KYN28-12 Armored Withdrawable AC Metal-Enclosed Switchgear - China Suppliers and Factory for High-Voltage Solutions
Basic Product Overview
KYN28-12 high-voltage switchgear cabinet (labeled as feeder cabinet) is a mainstream indoor metal-clad switchgear widely used in 10kV power distribution systems. As a core device in medium-voltage power grids, it undertakes the tasks of power receiving, distribution, fault protection, and operational monitoring, and is widely applied in substations, industrial and mining enterprises, commercial buildings, and urban power distribution networks.
The KYN28-12 cabinet (also known as KYN28A-12) adopts a withdrawable, compartmentalized metal-enclosed structure (complying with GB3906-2020 and IEC 62271-200 standards). Its design separates the cabinet into independent functional compartments through grounded metal partitions:
- Circuit Breaker Compartment — Houses the withdrawable vacuum circuit breaker
- Busbar Compartment — Encloses the main busbars for power distribution
- Cable Compartment — Manages incoming/outgoing cable connections
- Secondary Control Compartment — Contains protection relays, metering, and control devices
Application Scenarios
As a feeder cabinet, the KYN28-12 is mainly used to distribute power from the main busbar to downstream loads (e.g., transformers, motors, or other distribution cabinets). Typical application scenarios include:
- 🏭 Industrial Plants — Power distribution for high-power equipment (e.g., pumps, fans, production lines) in steel, chemical, and manufacturing industries.
- 🏢 Commercial Buildings — Power supply for lighting, air conditioning, and elevators in shopping malls, office buildings, and hospitals.
- ⚡ Urban Substations — 10kV distribution network outgoing lines, connecting to residential area transformers.
- 🌿 Renewable Energy Systems — Connecting wind/solar power generation units to the grid (with customized protection functions).
Core Technical Parameters
| Parameter | Specification / Value |
|---|---|
| ⚡ Rated Voltage | 12kV (adapted to 10kV power systems; maximum operating voltage: 12kV) |
| 🔄 Rated Frequency | 50Hz (matches the standard power grid frequency in most countries and regions) |
| 🔌 Rated Current — Main Circuit | 630A, 1000A, 1250A, 1600A (feeder scenarios typically use 630A / 1250A) |
| 🔌 Rated Current — Auxiliary Circuit | 220V / 380V (for powering control, protection, and monitoring components) |
| ⚡ Short-Time Withstand Current | ≥ 25kA (duration: 4s; withstands steady-state short-circuit current impact) |
| ⚡ Peak Withstand Current | ≥ 63kA (resists instantaneous peak current generated by short-circuit faults) |
| 🔒 Power Frequency Withstand Voltage | 42kV (1 min; between live parts and ground; between different phases) |
| ⛈ Lightning Impulse Withstand Voltage | 75kV (protects against overvoltage caused by lightning strikes or switching operations) |
| 🛡 IP Protection Grade | IP4X standard (IP54 available for harsh environments) |
| 🌡 Operating Temperature | -10°C to +40°C (derate by 1% per 1°C above 40°C) |
| ⛰ Altitude | ≤ 1000m (derating required above 1000m) |
| 💧 Humidity | Daily average ≤ 95%, monthly average ≤ 90% (no condensation) |