KYN28-12 Armored Withdrawable AC Metal-Enclosed Switchgear - High-Current Solution from China Suppliers & Factory
Basic Product Overview
KYN28-12 high-voltage switchgear cabinet (labeled as feeder cabinet) is a mainstream indoor metal-clad switchgear widely used in 10kV power distribution systems. As a core device in medium-voltage power grids, it undertakes the tasks of power receiving, distribution, fault protection, and operational monitoring, and is widely applied in substations, industrial and mining enterprises, commercial buildings, and urban power distribution networks.
The KYN28-12 cabinet (also known as "KYN28A-12") adopts a withdrawable, compartmentalized metal-enclosed structure. Its design separates the cabinet into independent functional compartments through grounded metal partitions:
- Circuit Breaker Compartment
- Busbar Compartment
- Cable Compartment
- Secondary Control Compartment
This compartmentalized design prevents fault expansion between compartments and improves the safety of operation and maintenance. The cabinet model "KYN28-12" is applicable to 12kV systems, functioning as a feeder cabinet responsible for distributing power from the main busbar to downstream equipment or lines.
Application Scenarios
The secondary circuit uses plug-in connectors, simplifying wiring and maintenance.
As a feeder cabinet, the KYN28-12 is mainly used to distribute power from the main busbar to downstream loads (e.g., transformers, motors, or other distribution cabinets). Typical application scenarios include:
- Industrial Industrial Plants: Power distribution for high-power equipment (e.g., pumps, fans, production lines) in steel, chemical, and manufacturing industries.
- Commercial Commercial Buildings: Power supply for lighting, air conditioning, and elevators in shopping malls, office buildings, and hospitals.
- Urban Urban Substations: 10kV distribution network outgoing lines, connecting to residential area transformers.
- Renewable Renewable Energy Systems: Connecting wind/solar power generation units to the grid (with customized protection functions).
Core Technical Parameters
- Main circuit: 630A, 1000A, 1250A, 1600A
- Auxiliary circuit: 220V / 380V
- Short-time withstand current: ≥25kA (4s)
- Peak withstand current: ≥63kA
- Power frequency withstand (1min): 42kV
- Lightning impulse withstand: 75kV
- Temperature: -10°C to +40°C (derating 1% per °C above 40°C)
- Altitude: ≤1000m (derating required above 1000m)
- Humidity: Daily average ≤95%, monthly average ≤90% (no condensation)